PFP Logo

12,000 gallons of Turbine Reservoir Oil filtered during 2-day outage

Nov 12, 2020 | Maintenance, Oil Quality & Purification, Power Generation

  1. Home
  2. Maintenance
  3. 12,000 gallons of Turbine Reservoir Oil filtered during 2-day outage

High-Velocity Flushing SkidHere we are back again with some more notes from the industrial filtration field…

This time a power generation facility in central Pennsylvania needed their turbine reservoir oil cleaned during a scheduled outage. Approximately 12,000 gallons of oil need to be cleaned from ISO 4406 22/20/16 to ISO 4406 17/15/12 or better.

Day 1: Utilizing one of our variable-flow 600 GPM flushing skids and a portable laser particle counter, we hooked up to the reservoir and started flowing. After just two hours the ISO codes started dropping, almost to the desired cleanliness code by the end of day one.

Day 2: We started flushing the oil at 7:00 A.M. and we were able to clean the oil to ISO 14/13/9 by 1:00 P.M.  After breaking down the system and cleaning up we started our journey home by day’s end… another success story!

Do YOU have any questions about our on-site flushing services or about filtering turbine reservoir oil?

Here at PFP, I actually manage the operations, including all types of equipment rental services.

Feel free to get in touch with us and ask to speak with me directly.

— Matt @ PFP

Contact an Expert

Need assistance? PFP will help you solve your industrial filtration challenges.

1-888-679-6645 / sales@pfpusa.com

Related Blog Posts

How Often Should Generator Fuel Be Tested?

How Often Should Generator Fuel Be Tested?

Drop us a follow on social media!TL;DR - Generator fuel should be tested at least once per year to check for water, microbial growth, and particulate contamination. Critical facilities like hospitals and data centers often test every 6 months or quarterly to ensure...

Lube Oil Contamination: Vacuum Dehydrator Rental Solutions

Lube Oil Contamination: Vacuum Dehydrator Rental Solutions

Lube Oil Contamination SolutionsThis case study explains how PFP mobilized a vacuum dehydrator rental within 24 hours to address water and particulate contamination in a paper mill lube oil reservoir.Recently, we were contacted by a manufacturer in the paper industry...

HIAC PODS Discontinued: Replacement Options

HIAC PODS Discontinued: Replacement Options

We offer a variety of replacement options for Beckman Coulter's discontinued HIAC PODS Particle Counter.If you landed here looking for a Beckman Coulter HIAC PODS recalibration, rental, or purchase option, you're not alone. We hear from customers all the time who...

Follow us on social media!

Contact an Expert

Need assistance? PFP will help you solve your industrial filtration challenges.

1-888-679-6645 / sales@pfpusa.com

Want the most up to date information from PFP?

Sign up for our E-mail newsletter!